DSE6020
Auto Mains Failure Control Module
|
|
Overall Size
|
216 mm x 158 mmx 43mm
(7.5″ x 6.2″ x 1.5″)
|
Panel Cutout Size
|
184 mm x 137 mm
(7.2″ x 5.3″)
|
Maximum Panel Thickness
|
8.0 mm (0.3″)
|
Package Size
|
275mm*185mm*50mm
|
Weight(NW)
|
0.48kg
|
DC SUPPLY
|
CONTINUOUS VOLTAGE RATING
|
8 V to 35 V Continuous
|
MAXIMUM OPERATING CURRENT
|
100 mA at 12 V, 105 mA at 24 V
|
|
MAXIMUM STANDBY CURRENT
|
60 mA at 12 V, 55 mA at 24 V
|
|
MAXIMUM SLEEP CURRENT
|
40 mA at 12 V, 35 mA at 24 V
|
|
MAINS (UTILITY)
|
VOLTAGE RANGE
|
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
|
FREQUENCY RANGE
|
3.5 Hz to 75 Hz
|
|
OUTPUTS
|
OUTPUT A (FUEL)
|
10 A short term, 5 A continuous, at supply voltage |
OUTPUT B (START)
|
10 A short term, 5 A continuous, at supply voltage |
|
AUXILIARY OUTPUTS C ,D,E& F
|
2 A DC at supply voltage
|
|
GENERATOR
|
VOLTAGE RANGE
|
15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) |
FREQUENCY RANGE
|
3.5 Hz to 75 Hz
|
|
MAGNETIC PICK-UP
|
VOLTAGE RANGE
|
+/- 0.5 V to 70 V
|
FREQUENCY RANGE
|
10,000 Hz (max)
|