DSE7220
Auto Mains Failure Control Module
|
|
Overall Size
|
240 mm x 184 mmx42mm
(9.4″ x 7.1″ x 1.6″)
|
Panel Cutout Size
|
220 mm x 160 mm
(8.7″ x 6.3″)
|
Maximum Panel Thickness
|
8.0 mm (0.3″)
|
Product Size
|
286mm*190mm*50mm
|
Weight
|
0.92kg
|
DC SUPPLY
|
CONTINUOUS VOLTAGE RATING
|
8 V to 35 V Continuous
|
MAXIMUM OPERATING CURRENT
|
340 mA at 12 V, 160 mA at 24 V
|
|
MAXIMUM STANDBY CURRENT
|
160 mA at 12 V, 80 mA at 24 V
|
|
CHARGE FAIL/EXCITATION RANGE
|
0 V to 35 V
|
|
MAINS (UTILITY)
|
VOLTAGE RANGE
|
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
|
FREQUENCY RANGE
|
3.5 Hz to 75 Hz
|
|
OUTPUTS
|
OUTPUT A (FUEL)
|
15 A DC at supply voltage
|
OUTPUT B (START)
|
15 A DC at supply voltage
|
|
OUTPUTS C & D
|
8 A 250 V (Volt free)
|
|
AUXILIARY OUTPUTS E,F,G,H
|
2 A DC at supply voltage
|
|
GENERATOR
|
VOLTAGE RANGE
|
15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) |
FREQUENCY RANGE
|
3.5 Hz to 75 Hz
|
|
MAGNETIC PICK-UP
|
VOLTAGE RANGE
|
+/- 0.5 V to 70 V
|
FREQUENCY RANGE
|
10,000 Hz (max)
|